Viessmann Boiler: Maintenance message comes back on Monday morning
Maintenance message comes back on Monday morning on a Viessmann boiler: After a service, the maintenance message can return on the next Monday morning if coding 24 is not reset. This applies to both control units when the Vitocontrol-S is used.
Applies to: Vitotronic 100 GC1 with Vitocontrol-S
Common causes of maintenance message comes back on monday morning
- Coding 24 on Vitotronic 100 GC1 was not reset to 0 after maintenance.
How to fix maintenance message comes back on monday morning: step by step
- Set coding 24 to 1 and then back to 0 on the Vitotronic 100 GC1 if maintenance was done before the message appeared.
- After maintenance, set coding 24 to 0 on the Vitotronic 100 GC1.
- Acknowledge the maintenance display on both control units if required.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 107. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.