Viessmann Boiler: LON participant number and participant list update (single-boiler)
LON participant number and participant list update (single-boiler) on a Viessmann boiler: Single-boiler systems only. The LON communication module accessory must be fitted (see p. 111). The LON participant number is set with coding address 77 in coding level 1; factory setting is 77:1. Each number may be used only once in a LON BUS system. The control must be coded as error manager (79:1) to update the participant list, and all participants must be connected.
Applies to: Single-boiler systems with Vitotronic 100 GC1 on LON BUS
How to fix lon participant number and participant list update (single-boiler): step by step
- Fit the LON communication module.
- Set the participant number with coding 77 in coding level 1.
- Code the control as error manager with coding 79:1 if it will manage the list.
- Press the two buttons shown on p. 87 together for about 2 seconds.
- Press D to start the participant check.
- Wait about 2 minutes for the participant list to update.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.