Viessmann Boiler: LON bus wiring and cable limits
LON bus wiring and cable limits on a Viessmann boiler: LON runs in line topology with a terminator at each end. Use only one cable type per LON.
Applies to: Vitotronic 300 GW6B and Vitocom on LON
How to fix lon bus wiring and cable limits: step by step
- Use one cable type within one LON.
- Allowed on-site cable: 2-core CAT5 screened, or JY(St)Y 2 x 2 x 0.8 mm telephone cable.
- Use RJ45 connectors. Cores 1 and 2 plus the screen are required. The cores can be swapped.
- Direct connection with Viessmann LON cable: line up to 23 ft (7 m).
- Installation spacing 23 to 69 ft (7 to 21 m): use the Viessmann LON cable and a LON coupling. Max 3 cables between 2 appliances.
- On-site cable with LON plug: line up to 3000 ft (900 m), up to 30 participants.
- On-site cable with LON junction boxes: line up to 3000 ft (900 m).
- Fit a terminal end resistor at each end of the line.
- Follow the cabling requirements for the FTT 10-A LON interface.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.