Viessmann Boiler: Leak test on boiler and flue gas path
Leak test on boiler and flue gas path on a Viessmann boiler: Check gaskets and components that carry flue gas for leaks while the boiler runs.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
Common causes of leak test on boiler and flue gas path
- Failed gasket on burner plate
- Failed seal on flue gas collector
- Leak at heating water connections or low-water indicator connections
How to fix leak test on boiler and flue gas path: step by step
- Check the heating system pressure (8 to 160 psi).
- Inspect gaskets with an inspection mirror during operation, or with a dew point hygrometer at full load.
- Remove thermal insulation parts if needed.
- Look for condensate traces on the flue gas collector or insulation. These also show leaks.
- Check connections for control equipment and the minimum pressure monitor for leaks.
- Check all heating water connections for leaks about every 500 operating hours.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B service instructions, p. 11, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.