Viessmann Boiler: Install the boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3 only)
Install the boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3 only) on a Viessmann boiler: A 120 V or 24 V valve adaptor is mounted on the DIN rail inside the connection enclosure. Operating time is set on coding address 40 (5 to 199 sec).
Applies to: Boiler return mixing valve or modulating valve actuator
How to fix install the boiler return mixing valve or modulating valve actuator (vd2/vd2a/ct3 only): step by step
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Insert plug gS into socket gS on the control.
- Secure the cable with a tie (see page 21).
- Connect the black adaptor wire to terminal aBH on the DIN rail (terminal 8, 9 or 10).
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
- Set the valve operating time on coding address 40 (5 to 199 sec).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 Installation and Service Instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.