Viessmann Boiler: Install boiler pressure relief and air vent
Install boiler pressure relief and air vent on a Viessmann boiler: Set up the safety header and discharge piping on the boiler.
Applies to: All models
How to fix install boiler pressure relief and air vent: step by step
- Apply pipe sealant to both ends of fittings B, D, F and G and install onto coupling A and tees C.
- Install the pressure relief valve and the air vent, then tighten.
- Run the relief discharge pipe to a floor drain and end it about 6 in. (150 mm) above the drain.
- Do not install a shutoff valve in the discharge pipe, do not reduce its diameter, and do not pipe it to outdoors.
- Keep the discharge pipe end unthreaded and oriented to prevent scalding.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A installation instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.