Viessmann Boiler: Install and check DHW tank temperature sensor
Install and check DHW tank temperature sensor on a Viessmann boiler: The sensor measures DHW tank temperature. Leave it unconnected on systems without DHW heating.
Applies to: DHW tank temperature sensor
How to fix install and check dhw tank temperature sensor: step by step
- Install the DHW tank sensor following the domestic hot water tank instructions.
- On DHW tanks of other makes, press the sensor against the sensor well with a suitable device.
- Make sure the maximum allowed DHW temperature is not exceeded; add a suitable safety device if needed.
- Disconnect plug in the boiler control terminal compartment.
- Measure sensor resistance at plug terminals 1 and 2 and compare with the tank temperature.
- If the value differs significantly, check installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100
Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.