Viessmann Boiler: Inspect and replace burner mesh assembly and refractory
Inspect and replace burner mesh assembly and refractory on a Viessmann boiler: Replace the burner mesh assembly if the wire mesh is damaged.
Applies to: Vitocrossal 300 CU3A burner head
Common causes of inspect and replace burner mesh assembly and refractory
- Damaged wire mesh
- Damaged refractory
How to fix inspect and replace burner mesh assembly and refractory: step by step
- Remove electrodes A.
- Remove the four nuts D and take off the fan with gas valve C.
- Remove the three nuts B and take off the burner mesh assembly H.
- Remove refractory F with thermal insulating mat E.
- Remove old burner mesh gasket G.
- Check refractory F and replace if damaged.
- Fit thermal insulating mat E and refractory F per electrode position, using the positioning aid.
- Fit new burner mesh assembly H with new gasket G and secure with three nuts.
- Fit the fan with gas valve.
- Do not damage the burner head wire gauze.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.