Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Heating system fill water and antifreeze

Updated · by Aurora Star Tech Inc.

Heating system fill water and antifreeze on a Viessmann boiler: Treat boiler water where minerals or hardness are high. The boiler suits only closed hot water systems with pumps. Antifreeze is allowed up to a 50/50 mix, and 40% gives freeze protection to -10°F (-23°C). Use only antifreeze made for hydronic heating; never automotive glycol. Antifreeze can require a backflow preventer on the feed and can affect expansion tanks and radiation, so check the system often.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

How to fix heating system fill water and antifreeze: step by step

  1. Flush the existing heating system before connecting the new boiler to remove dirt and sludge.
  2. Fill the boiler with suitable water only and bleed all air.
  3. Keep the cold water fill pressure at 18-20 psig maximum and equal to the expansion tank pressure.
  4. Check all connections, including those under insulation, for leaks before fitting insulation.
  5. Install boiler isolation valves and drain valves above them on the supply and return.
  6. If the boiler heats an indirect DHW tank, fit flow check valves on the pump discharge of loops without a mixing valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 44. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977