Viessmann Boiler: Heating system design version 7: heating circuit plus low temperature circuit with Vitorond on shunt pump
Heating system design version 7: heating circuit plus low temperature circuit with Vitorond on shunt pump on a Viessmann boiler: Vitocrossal 300 CT3 as lead boiler and Vitorond 200 VD2 as lag boiler, operated by a Viessmann control system with outdoor reset, modulating boiler water temperature and load-dependent sequential control. Return temperature control for the Vitorond uses the shunt pump and closing the isolation valve. Sensor T1 controls the isolation valve. Sensor T2 switches the shunt pump. Boiler supply temperature is set automatically over LON BUS.
Applies to: Heating system design version 7
How to fix heating system design version 7: heating circuit plus low temperature circuit with vitorond on shunt pump: step by step
- Set the coding for system version 7 on every Vitotronic 100 GC1.
- Set the Vitocontrol-S coding as listed in the system version 7 coding table.
- For the low temperature boiler, connect temperature sensor T1 to plug aJA and temperature sensor T2 to plug aJB.
- Connect at least 15% of the rated output of the Vitocrossal 300 to the lower return connection. Provide return temperature control as an accessory or on site.
- Check the connection diagram on site for completeness and function.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 22-24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.