Viessmann Boiler: Heating system design version 4: return temperature control with three-way mixing valve
Heating system design version 4: return temperature control with three-way mixing valve on a Viessmann boiler: Multi-boiler cascade with a Vitocontrol-S controlling Vitotronic 100 GC1 boiler controls via LON. Used for older heating systems, systems in nurseries, or systems where downstream heating circuits cannot be controlled. Sensor T1 closes the three-way mixing valve in proportion to protect the boiler when the required minimum return temperature is not reached.
Applies to: Heating system design version 4 (Vitotronic 100 GC1 with Vitocontrol-S VD2/CT3/CM2)
How to fix heating system design version 4: return temperature control with three-way mixing valve: step by step
- Set the coding listed in the system version 4 coding table on every Vitotronic 100 GC1.
- Set the Vitocontrol-S coding as listed in the same table.
- Connect temperature sensor T1 to plug aJA.
- Size each boiler circuit pump so its volume flow is at least the maximum total heating circuit volume flow (recommendation: 110%).
- Check the connection diagram on site for completeness and function. Single-phase and three-phase pumps need field-supplied motor contactors or starters.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.