Viessmann Boiler: Gas piping pressure test
Gas piping pressure test on a Viessmann boiler: Test gas piping and remove air before the boiler is put into operation.
Applies to: All models
How to fix gas piping pressure test: step by step
- Isolate the boiler from the gas piping using its manual shutoff valve for tests at or below ½ psig (14 in. w.c.).
- Disconnect the boiler and its shutoff valve for tests above ½ psig (14 in. w.c.).
- Perform the leak test with approved liquid spray solution.
- Keep leak fluid off electrical parts, wires and connectors, and off the gas valve regulator and its vent opening.
- Correct all leaks found.
- Purge air from the gas line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A installation instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.