Viessmann Boiler: Gas piping installation and leak test

Updated · by Aurora Star Tech Inc.

Gas piping installation and leak test on a Viessmann boiler: Size the gas pipe from the run length, number of fittings, gas type and total input of all gas appliances, following CAN/CSA B149.1 and .2 or NFPA 54 / ANSI Z223.1. Keep piping clear of serviceable components. Test pressure that is too high can damage the burner and gas fittings. Do not vent gas piping above the combustion chamber.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

How to fix gas piping installation and leak test: step by step

  1. Before connecting the boiler, install a ground joint union, a capped drip leg and a manual shut-off valve listed by a recognized testing agency.
  2. Connect the NG line to the NG shut-off valve and the LPG line to the LPG shut-off valve.
  3. Leak test the piping with an approved method.
  4. Purge the gas line safely with an approved purge burner.
  5. Install a gas filter if the gas pipe may contain dirt.
  6. Tag the shut-off valves and explain them to the owner.
  7. Open the manual gas valve, leak test all connections with a certified leak detector, close the valve, and repair any leaks.
  8. Repeat the valve leak test for the other fuel.
  9. Install the drip pocket per CAN/CSA B149.1 or NFPA 54.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 42-43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair