Viessmann Boiler: Flow switch test
Flow switch test on a Viessmann boiler: The boiler has a flow sensing device. If flow is too low, the switch opens, the burner shuts down and it will not restart until adequate flow returns.
Applies to: Vitodens 200 B2HA/B2HB boilers with flow switch
How to fix flow switch test: step by step
- Throttle the water flow to or from the boiler.
- Confirm the boiler shuts down once flow drops below its safe operating set point.
- Restore flow and confirm the burner restarts.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.