Viessmann Boiler: Fixed high limit test by jumper (alternate method)

Updated · by Aurora Star Tech Inc.

Fixed high limit test by jumper (alternate method) on a Viessmann boiler: Alternate CSD-1 method that runs the boiler at high fire with the boiler valve closed until the fixed high limit trips.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB boilers where CSD-1 testing is required

How to fix fixed high limit test by jumper (alternate method): step by step

  1. Close the boiler valve and jumper across the flow switch.
  2. Run the boiler at high fire. The boiler is shut down by the coding card (on B2TB models, set coding address 06 to maximum).
  3. Keep the boiler temperature rising until the fixed high limit trips.
  4. Slowly open the boiler valve to cool the boiler down safely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.