Viessmann Boiler: Fixed high limit test #1 (F2 simulation with boiler pump disconnected)
Fixed high limit test #1 (F2 simulation with boiler pump disconnected) on a Viessmann boiler: Test that trips the manual reset high limit by running the burner with the boiler pump disconnected. Viessmann is not responsible for damage caused by overheating during this test.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix fixed high limit test #1 (f2 simulation with boiler pump disconnected): step by step
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner is lit, unplug the boiler pump from the control board carefully.
- Watch the boiler temperature rise. The burner shuts off and the temperature should keep climbing.
- At about 210°F (99°C) the limit trips and shows F2.
- If the limit is not reached, wait two minutes after burner shutoff, then energize the pump for no more than 1 second. Repeat as needed.
- For boilers with flow switches (sizes 19 to 100), the switches may need to be jumpered during the test.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.