Viessmann Boiler: Filling the heating system
Filling the heating system on a Viessmann boiler: Fill and vent the heating system with the expansion vessel and fill pressure set correctly.
Applies to: Vitocrossal 300 CU3A start-up
How to fix filling the heating system: step by step
- With the system cold, check the expansion vessel pre-charge.
- If pre-charge is below static pressure, top up with nitrogen until it is 1.5 to 3 psi (0.1 to 0.2 bar) above static pressure.
- Close the gas shutoff valve.
- Open any installed shutoff valves.
- Fill the system with water through the boiler drain/fill valve and vent it.
- Fill until the fill pressure is 1.5 to 3 psi (0.1 to 0.2 bar) above the expansion vessel pre-charge.
- Mark the set pressure on the gauge.
- Return shutoff valves to operating position.
- Close the drain/fill valve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A service instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.