Viessmann Boiler: Fill and pressurise the heating system
Fill and pressurise the heating system on a Viessmann boiler: Set the expansion vessel precharge first, then fill and vent the system at the correct pressure.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix fill and pressurise the heating system: step by step
- With the system cold, check the expansion vessel precharge. If it is lower than the static system pressure, top it up with nitrogen until it is 1.5 to 3 psi (0.1 to 0.2 bar) above static pressure.
- Close the gas shutoff valve.
- Open any installed shutoff valves.
- Fill the heating system with water and vent it, until the fill pressure is 1.5 to 3 psi (0.1 to 0.2 bar) above the vessel precharge, using the boiler drain/fill valve.
- Mark the set pressure on the temperature and pressure gauge.
- Record the fill volume, water hardness and pH value.
- Return the shutoff valves to their operating position.
- Close the boiler drain/fill valve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.