Viessmann Boiler: Field wiring rules for the boiler and controls
Field wiring rules for the boiler and controls on a Viessmann boiler: Wiring must follow the National Electrical Code (or CSA C22.1 in Canada) and local codes. Use Class 1 wiring, and sheath field-supplied 120 VAC wiring in flexible metal conduit.
Applies to: Hydrostat 3250-Plus control with Carlin or Beckett or Riello burners
How to fix field wiring rules for the boiler and controls: step by step
- Use 14 ga. or heavier wire for supply and control wiring.
- If replacing original boiler wire, use 105 C wire or equivalent.
- Provide electrical ground at the boiler as required by codes.
- Provide a disconnect, overload protection and low water cut-off as required by local codes.
- Connect incoming line voltage hot to L1 and neutral to L2 on the Hydrostat 3250-Plus.
- Turn off the power, including the boiler service switch, before any wiring work.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service manual, p. 29 and p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.