Viessmann Boiler: Field test of fixed high limit, simulation 2 (CSD-1)
Field test of fixed high limit, simulation 2 (CSD-1) on a Viessmann boiler: Checks the fixed high limit by running the boiler with minimal flow and then stopping flow completely. Only where required by law.
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
How to fix field test of fixed high limit, simulation 2 (csd-1): step by step
- Throttle the boiler valve until the burner runs with as little flow as possible.
- Run the boiler to high fire using the relays test.
- When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Let the boiler temperature keep rising until the fixed high limit trips.
- Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
- Reset the boiler control manually, since a tripped fixed high limit requires manual reset.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.