Updated · by Aurora Star Tech Inc.

Field test of fixed high limit, simulation 1 (CSD-1) on a Viessmann boiler: Checks the fixed high limit by overheating the boiler with the flow blocked. Only where required by law. Viessmann is not responsible for damage caused by overheating during this test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

How to fix field test of fixed high limit, simulation 1 (csd-1): step by step

  1. Close the boiler valve and jumper across the flow switch.
  2. Run the boiler at high fire. On B2TB models, set coding address 06 to maximum so the coding card shuts the burner down.
  3. Let the boiler temperature keep rising until the fixed high limit trips.
  4. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
  5. Reset the boiler control manually, since a tripped fixed high limit requires manual reset.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125

Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.