Viessmann Boiler: External shut-off via terminal aBÖ (safety switch-off only)
External shut-off via terminal aBÖ (safety switch-off only) on a Viessmann boiler: A dry contact on terminal aBÖ gives a controlled switch-off. Use it only for safety switch-offs, such as a high limit thermostat.
Applies to: VD2, VD2A, CT3 boilers
How to fix external shut-off via terminal abÖ (safety switch-off only): step by step
- Remove the jumper between terminals 16 and 17.
- Connect the dry contact. Controlled switch-off happens when the contact opens.
- For emergency operation, move the jumper from terminals 16 and 17 to terminals 17 and 18.
- See page 52 for details of controlled switch-off.
- Warning: during switch-off there is no frost protection for the heating system and the boiler is not held at minimum water temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.