Viessmann Boiler: External demand via switching contact
External demand via switching contact on a Viessmann boiler: Starts the burner on an external floating contact, subject to load. Connection is on plug aVH.2/aVH.3, or on the EA1 extension.
Applies to: Single boiler and cascade control units
How to fix external demand via switching contact: step by step
- Use a potential-free contact only.
- Single boiler: when the contact closes, the burner runs subject to load and heats to the boiler water setpoint in coding 9b (General group). Limiting is done by that setpoint and by the boiler water maximum in coding 06 (Combustion Controller group).
- Multi boiler: when the contact closes, each boiler burner runs subject to load and heats to the supply setpoint in coding 9b. Limiting is done by that setpoint and the supply maximum in coding 37 (Cascade group).
- Plug aVH: no coding change needed.
- EA1 extension: set 5d (DE1), 5e (DE2) or 5f (DE3) in the General group to 2.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.