Viessmann Boiler: External changeover between staged and modulating burner
External changeover between staged and modulating burner on a Viessmann boiler: A dry contact on plug aVH switches the burner between two-stage and modulating operation.
Applies to: Staged/modulating burner changeover
How to fix external changeover between staged and modulating burner: step by step
- Connect a dry contact to terminals 1 and 2 of plug aVH.
- Contact open: modulating operation.
- Contact closed: two-stage operation.
- Set the burner type to modulating in coding 1 (coding "02: 2").
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.