Viessmann Boiler: External blocking via switching contact
External blocking via switching contact on a Viessmann boiler: Blocks the boiler or cascade from an external floating contact. Connection is on plug aVD.2/aVD.3, or on the EA1 extension for cascade control units.
Applies to: Single boiler and cascade control units
How to fix external blocking via switching contact: step by step
- Use a potential-free contact only.
- Single boiler: when the contact closes, the boiler shuts down.
- Multi boiler: when the contact closes, the burners are shut down in a controlled way on each boiler, and any connected circuit or system pump stops. Shut-off devices close.
- The heating system has no frost protection while blocked.
- On plug aVD: set coding 99 in the General group to decide what the input influences. Never change coding 99:0 in a cascade control unit.
- On EA1 extension: set 5d (DE1), 5e (DE2) or 5f (DE3) in the General group to 3 or 4.
- In cascade control units, make the connection on the EA1 extension.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.