Viessmann Boiler: Electrical installation checklist
Electrical installation checklist on a Viessmann boiler: Electrical work must follow local codes and be done by a qualified electrician.
Applies to: Vitotron 100 VLN2 electrical
How to fix electrical installation checklist: step by step
- Ground the boiler per the National Electrical Code or local code.
- Power the heating elements from a 240 VAC single phase supply.
- Run a separate 120 VAC, 15 A circuit for the circulating pump and keep it separate from thermostat and low voltage wires.
- Tighten all connections with a 3/16 in. hex key.
- Check every electrical connection is tight before starting the boiler.
- Use copper wire only and size breakers and conductors from the nameplate.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4
Source: Vitotron 100 VLN2 installation and service instructions, p. 10-11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.