Viessmann Boiler: Dismantling the burner
Dismantling the burner on a Viessmann boiler: Removing the upper burner section and the burner tube.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner
How to fix dismantling the burner: step by step
- Close the gas shut-off valve and let the system cool. Follow the preparing-for-service section on page 51.
- Disconnect the burner gas line and the connectors on the burner control unit.
- Pull off the ignition electrode connectors.
- Remove 2 screws from the ignition electrode block and lift the block up and out.
- Remove the 6 nuts around the burner mounting plate and remove the upper burner section.
- Secure lifting chains at 3 points on the frame of the upper burner section.
- Remove the 8 nuts from the combustion chamber cover plate.
- Lift out the mounting plate with the burner tube using a lifting device, following the lifting device instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 69-70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.