Viessmann Boiler: DHW tank piping and non-Viessmann tanks
DHW tank piping and non-Viessmann tanks on a Viessmann boiler: DHW supply and return piping between the boiler and a Viessmann DHW tank must be at least 1 1/4 in. For non-Viessmann tanks, calculate the DHW coil pressure drop against the field supplied pump residual head to confirm enough flow reaches the boiler heat exchanger. Insufficient flow can cause short cycling and poor DHW supply. If a tank other than a Viessmann Vitocell 100 or 300 is used, verify the Viessmann DHW sensor operation with the tank manufacturer. A temperature tempering valve in the DHW supply line is strongly recommended.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix dhw tank piping and non-viessmann tanks: step by step
- Use at least 1 1/4 in. piping between the boiler DHW connections and the Viessmann tank.
- For non-Viessmann tanks, calculate the coil pressure drop against pump residual head.
- Verify DHW sensor operation with the original tank manufacturer.
- Install a temperature tempering valve in the DHW supply line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.