Viessmann Boiler: DHW piping size and flow for tank applications
DHW piping size and flow for tank applications on a Viessmann boiler: DHW supply and return piping must be sized so the field pump has enough head to push water through the tank coil and the boiler heat exchanger. Undersized piping can cause short-cycling and poor DHW supply.
Applies to: Vitocrossal 300 CU3A with DHW storage tank
How to fix dhw piping size and flow for tank applications: step by step
- Use at least 1¼ in. pipe between the boiler DHW connections and the Viessmann DHW tank connections.
- With a non-Viessmann tank, calculate the tank coil pressure drop against the field pump's residual head.
- Confirm enough flow reaches the boiler heat exchanger.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2635455794125160199CU3ACU3A 26CU3A 35CU3A 45CU3A 57CU3A 94CU3A 125CU3A 160CU3A 199Vitocrossal 300, type CT3
More commissioning tips for boiler
Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.