Viessmann Boiler: Dew-point protection with two-stage burner and Vitotronic control
Dew-point protection with two-stage burner and Vitotronic control on a Viessmann boiler: With a Vitotronic control in modulating mode, the burner must be able to reach full input to protect the boiler from dew-point corrosion.
Applies to: VD2-320 to VD2-1080 with two-stage burner and Vitotronic control
Common causes of dew-point protection with two-stage burner and vitotronic control
- Boiler water falls below 140°F (60°C) and condensation forms
- Burner is limited to first stage in summer
How to fix dew-point protection with two-stage burner and vitotronic control: step by step
- Set the first-stage minimum input of the two-stage burner as specified in the burner instructions.
- Do not limit the burner to first-stage operation during summer months.
- Confirm flue gas temperature at partial load is at least 248°F (120°C). Required value depends on chimney insulation and height.
- With a two-stage burner, the burner should switch to full input automatically when boiler water drops below 140°F (60°C).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.