Viessmann Boiler: Determine values for a two-stage burner
Determine values for a two-stage burner on a Viessmann boiler: Measure maximum and basic burner output so the values can be entered in coding 1.
Applies to: Vitotronic 100 GC1 with two-stage burner
How to fix determine values for a two-stage burner: step by step
- Start up the burner.
- Set the override switch to the position shown in the manual.
- Determine the maximum burner output from fuel consumption and record the value.
- Set the override switch to position a.
- Press buttons 9 and the second button together for about 2 seconds to start the relay test.
- Activate burner stage 1 ON with the stage button (display shows 4).
- Determine the minimum burner output (basic load) from fuel consumption and record the value.
- Press the button to complete the relay test.
- Enter the recorded values in coding 1 (addresses 08, 09 and 0A) as shown in the table.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 96. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.