Viessmann Boiler: CSD-1 fixed high limit fault simulation #2 (flow switch jumpered)
CSD-1 fixed high limit fault simulation #2 (flow switch jumpered) on a Viessmann boiler: Alternate high limit test with the boiler valve closed and the flow switch bypassed. Viessmann is not responsible for damage caused by overheating during this test.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix csd-1 fixed high limit fault simulation #2 (flow switch jumpered): step by step
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. It shuts down through the coding card, but the temperature should keep rising until the fixed high limit trips.
- When the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
- On B2TB models only, set coding address 06 to maximum to force the shutdown.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.