Viessmann Boiler: CSD-1 fixed high limit fault simulation #2 (flow switch jumpered)

Updated · by Aurora Star Tech Inc.

CSD-1 fixed high limit fault simulation #2 (flow switch jumpered) on a Viessmann boiler: Alternate high limit test with the boiler valve closed and the flow switch bypassed. Viessmann is not responsible for damage caused by overheating during this test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

How to fix csd-1 fixed high limit fault simulation #2 (flow switch jumpered): step by step

  1. Close the boiler valve.
  2. Jumper across the flow switch.
  3. Run the boiler at high fire. It shuts down through the coding card, but the temperature should keep rising until the fixed high limit trips.
  4. When the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
  5. On B2TB models only, set coding address 06 to maximum to force the shutdown.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.