Viessmann Boiler: CSD-1 fixed high limit fault simulation #1 (pump removed)
CSD-1 fixed high limit fault simulation #1 (pump removed) on a Viessmann boiler: Test of the fixed high limit switch, required where CSD-1 applies. Viessmann is not responsible for damage caused by overheating during this test.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 with boiler pump plug at control board
How to fix csd-1 fixed high limit fault simulation #1 (pump removed): step by step
- Confirm the boiler and boiler pump are in normal operating condition.
- Remove the cover from the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go into high fire.
- Once the burner ignites, unplug the boiler pump from the control board.
- Watch the boiler temperature rise and the burner shut off.
- Confirm the temperature continues to rise to 210°F (99°C), where the high limit trips and generates an F2 fault.
- If the limit is not reached, wait two minutes after the burner shuts off, then energize the pump for no more than 1 second by plugging it in. Repeat as needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.