Updated · by Aurora Star Tech Inc.

CSD-1 field test of fixed high limit (where required by law) on a Viessmann boiler: Field test procedure for the fixed high limit on Vitodens boilers. Viessmann is not responsible for damage caused by overheating during this test. A tripped fixed high limit gives a fault that needs a manual reset on the boiler control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

How to fix csd-1 field test of fixed high limit (where required by law): step by step

  1. Simulation 1: close the boiler valve and jumper across the flow switch.
  2. Simulation 1: run the boiler at high fire. It shuts down through the coding card (on B2TB models set coding address 06 to maximum) but the temperature should keep rising until the fixed high limit trips.
  3. Simulation 1: once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
  4. Simulation 2: throttle the boiler valve so the burner runs with as little flow as possible.
  5. Simulation 2: run the boiler to high fire using the relay test.
  6. Simulation 2: when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  7. Simulation 2: the temperature should keep rising until the fixed high limit trips. Then slowly open the boiler valve to cool the boiler down.
  8. Simulation 3: disconnect one of the wires on the limit switch. This creates a fault that requires a manual reset of the control.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125

Source: Vitodens 222-F, B2TB service instructions, p. 7. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977