Viessmann Boiler: Control calls for heat but the burner does not respond
Control calls for heat but the burner does not respond on a Viessmann boiler: The control is calling for heat but the burner stays off.
Applies to: Vitotronic 100 KW10B
Common causes of control calls for heat but the burner does not respond
- Burner is faulty and will not reset
- Power venter has no separate 120 VAC supply to its motor
- Air proving switch, blower wheel or timer/relay in the power venter is defective
- Another accessory is defective
How to fix control calls for heat but the burner does not respond: step by step
- Try to reset the burner with the reset button under the burner hood. Service the burner if needed and check the burner manual troubleshooting section.
- Make sure the power venter has its own 120 VAC supply to the motor. Check the power venter manual troubleshooting section.
- Check that all accessories work properly and replace any that do not. Use the accessory literature for guidance.
- If the F1 fuse has blown, replace it.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.