Viessmann Boiler: Control calls for heat but burner does not respond
Control calls for heat but burner does not respond on a Viessmann boiler: The control is calling for heat but the burner or power venter does not run. Work through the burner, the power venter and the accessories.
Applies to: Vitotronic 100 KW10B with burner and power venter
Common causes of control calls for heat but burner does not respond
- Burner is locked out or faulty
- Power venter has no separate 120 VAC supply to its motor
- Air proving switch, blower wheel or timer/relay in the power venter is defective
- Other accessory defect
- Fuse F1 has blown
How to fix control calls for heat but burner does not respond: step by step
- Reset the burner with the reset button under the burner hood.
- If the burner still does not respond, service it and see the troubleshooting section of the burner manual.
- Confirm the power venter has its own 120 VAC supply to the motor; see the power venter instructions.
- If the power venter still does not run, check the air proving switch, blower wheel and timer/relay per the power venter manual.
- Check all accessories operate properly and replace any that do not, using their supplied literature.
- If F1 has blown, replace it.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100, KW10B Operating and User's Information manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.