Viessmann Boiler: Connect the vent to the boiler
Connect the vent to the boiler on a Viessmann boiler: Venting must be short and straight with a supported horizontal run. Use the factory vent adaptor on the flue gas collar.
Applies to: VR1 22 to 33, 91 to 140
How to fix connect the vent to the boiler: step by step
- Route the vent the shortest way with the fewest elbows. Rearrange water piping if needed for a closer chimney connection.
- Support horizontal runs so they do not sag, and avoid long horizontal runs.
- Give horizontal runs at least 1/4 in rise per ft from the boiler to the vent terminal.
- Strap horizontal runs every 4 ft (1.2 m) with metal strapping.
- Attach the factory vent pipe adaptor to the flue gas collar with three equally spaced corrosion resistant self-tapping screws and high temperature silicone, or equivalent.
- Connect the chimney through a field supplied 18 in (457 mm) long, slightly inclined intermediate section of 5 in outside diameter flue pipe.
- Drill a 1/2 in opening on the side of the vent pipe, about three times the vent pipe diameter from the flue collar, for flue gas analysis.
- Seal all flue pipe joints.
- Insulate any uninsulated vent pipe to reduce flue gas cooling and noise.
- Install an outside rain cap and use a field supplied M-barometric damper for oil, per the draft control maker's instructions.
- In Canada, fit the blocked vent safety switch. For direct vent, follow the separate direct vent instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.