Viessmann Boiler: Connect power supply
Connect power supply on a Viessmann boiler: Supply is 120 VAC, 1 PH, 60 Hz. The control must be grounded.
Applies to: Control unit power supply
How to fix connect power supply: step by step
- Make sure the main supply to the control has overcurrent protection of at least 6 A and a 2-pole disconnect.
- Provide disconnect means and overcurrent protection as per local codes.
- Connect the supply wire to terminals 11, N and G on the DIN rail in the connection enclosure.
- Do not interchange L, N and G.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100
Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.