Viessmann Boiler: Connect flue gas and combustion air
Connect flue gas and combustion air on a Viessmann boiler: Connect the flue and combustion air pipes with the shortest practical run and secure them. The boiler flue collector cannot carry the venting weight.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix connect flue gas and combustion air: step by step
- Fit an on-site support immediately downstream of the boiler flue connection.
- Connect the flue outlet to the flue pipe with the shortest run, with a slight rise (minimum 3 degrees), and avoid sharp bends.
- Use the flue and combustion air sizes listed in the setting table for this section.
- Use a CPVC adaptor (80 mm to 3 in.) where the venting requires it.
- Secure combustion and exhaust pipes with the venting manufacturer's anchoring accessories.
- Follow the CU3A venting instructions for configurations and limits.
- Keep all pipework free of load and torque stress.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.