Viessmann Boiler: Connect an external 0-10 V boiler temperature signal
Connect an external 0-10 V boiler temperature signal on a Viessmann boiler: An external 0-10 V signal sets the maximum boiler water temperature. The signal must match the chart in the manual.
Applies to: Models 45, 57, 160, 199
How to fix connect an external 0-10 v boiler temperature signal: step by step
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check that the polarity is correct.
- Use the chart in the manual to find the maximum boiler water temperature for the signal.
- Example from the manual: 8 VDC = 176 ºF (80 ºC).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB installation instructions, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.