Viessmann Boiler: Connect a return mixing valve or modulating valve actuator (CM2 only)
Connect a return mixing valve or modulating valve actuator (CM2 only) on a Viessmann boiler: Wire a 120 V or 24 V valve actuator through a valve adaptor on the DIN rail inside the connection enclosure.
Applies to: CM2 only, return mixing valve or isolation/modulating valve actuator
How to fix connect a return mixing valve or modulating valve actuator (cm2 only): step by step
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Plug the gS plug into the gS socket on the control.
- Secure the cable with a tie (see page 45).
- Connect the adaptor's black wire to the 120 V L out terminal on the DIN rail (terminals 10, 11 or 12).
- Wire the valve actuator leads to the adaptor terminals as shown in the figures.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.