Viessmann Boiler: Connect a low water cut-off device
Connect a low water cut-off device on a Viessmann boiler: Wire the LWCO switch contact into the safety circuit at plug aBÖ.
Applies to: Vitotronic 300 GW6B
How to fix connect a low water cut-off device: step by step
- Remove the jumper between terminals 21(L) and 22(L).
- Connect the LWCO switching contact to terminals 21(L) and 22(L).
- Power the low water cut-off device from a free terminal 14, 15, 16 or 17 (L, N, G).
- Refer to the LWCO manufacturer manual for interconnection details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300, GW6B installation and service instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.