Viessmann Boiler: Connect a low gas pressure switch or external shut-off at terminal aBA

Updated · by Aurora Star Tech Inc.

Connect a low gas pressure switch or external shut-off at terminal aBA on a Viessmann boiler: Use a dry contact to switch the boiler off through the aBA terminals.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300 GW6B

How to fix connect a low gas pressure switch or external shut-off at terminal aba: step by step

  1. Remove the jumper between terminals 26 (L) and 27 (L).
  2. Connect the auxiliary low gas pressure switch or external shut-off (dry contact) to terminals 26 (L) and 27 (L).
  3. Refer to the low gas pressure switch installation instructions.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitotronic 300, GW6B installation and service instructions, p. 38. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.