Updated · by Aurora Star Tech Inc.

Connect 1st stage burner switch (plug aVD, terminals 1 and 2) on a Viessmann boiler: Dry contact that switches the basic-load burner stage.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: VD2/VD2A and CT3 with external modulation controller

How to fix connect 1st stage burner switch (plug avd, terminals 1 and 2): step by step

  1. Disconnect power before wiring.
  2. Connect a dry contact to terminals 1 and 2 of plug aVD.
  3. Contact closed: the 1st stage burner runs. On VD2/VD2A the full load only runs to hold minimum temperature, not with Vitocrossal 300.
  4. Water temperature is limited by the electronic max limit (coding 06) if set below the mechanical high limit R.
  5. Contact open: the 1st stage burner turns off.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 41, 43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.