Viessmann Boiler: Condensate drain installation

Updated · by Aurora Star Tech Inc.

Condensate drain installation on a Viessmann boiler: Route condensate through a P-trap or siphon so flue gas cannot enter the room. The boiler has a field-installed condensate trap, so no external trap is needed when the field drain connects to the P-trap. The external connection is a barb fitting, about 19 mm (inch size is garbled in the text). Use 1 in. diameter discharge tubing. The drain must end in an open or vented drain close to the boiler and must be visible for inspection. Do not tie in drains from other appliances such as a water softener backwash.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

How to fix condensate drain installation: step by step

  1. Connect the condensate drain to the boiler barb and fit a P-trap or siphon.
  2. Run 1 in. diameter CPVC, PVC or other approved drain pipe with a continuous fall toward the drain.
  3. Terminate the drain in an open or vented drain as close to the boiler as possible.
  4. If the boiler sits at ground level, keep the condensing drain max. 2 in. (50 mm) above ground.
  5. If the condensate outlet is below the drain, install an approved condensing-boiler pump with an overflow switch.
  6. Vent the pipe between the siphon trap and the neutralization unit if one is used.
  7. Use drain pipe and cement that meet ASTM D1785 or D2846 and ASTM D2564 or F493; in Canada use CSA or ULC listed schedule 40 CPVC or PVC.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.