Viessmann Boiler: Condensate disposal and neutralization
Condensate disposal and neutralization on a Viessmann boiler: Condensate from the boiler is acidic. Neutralize it before disposal if local rules require it.
Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
Common causes of condensate disposal and neutralization
- Condensate pH is about 3 to 4 (boiler) and within the 3 to 5.5 range given for the venting connection
How to fix condensate disposal and neutralization: step by step
- Check local building requirements for condensate disposal.
- If neutralizing is required, use a neutralization tank sized by Viessmann.
- Confirm treated condensate reads pH 6.5 to 9 before it goes to the drain.
- Condensate from the chimney can be collected with boiler condensate and sent to a floor drain.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.