Updated · by Aurora Star Tech Inc.

Combustion air device connection (VD2/VD2A/CT3) on a Viessmann boiler: Connect a combustion air blower through the combustion air device adaptor.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: VD2, VD2A and CT3 combustion air blower

How to fix combustion air device connection (vd2/vd2a/ct3): step by step

  1. Disconnect power to the control and burners.
  2. Mount the combustion air device adaptor (part no. 7134 563) on the DIN rail inside the connection enclosure, following the adaptor's manual.
  3. Remove the jumper between terminals 16 and 17.
  4. Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
  5. Wire the blower to the adaptor as shown in the diagram.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.