Viessmann Boiler: Combustion air device connection (CM2)
Combustion air device connection (CM2) on a Viessmann boiler: Connect a combustion air blower through the adaptor in the boiler junction box.
Applies to: CM2 combustion air blower
How to fix combustion air device connection (cm2): step by step
- Disconnect power to the control and burners.
- Mount the combustion air device adaptor (part no. 7134 563) on the DIN rail inside the boiler junction box, following the adaptor's manual.
- Remove plug 150 from the control, then remove the jumper between the two TR terminals.
- Using 14 AWG field wire, connect neutral to terminal 16, TR (left) to terminal 18, and TR (right) to terminal 19.
- Reinstall plug 150 and the DIN rail connections as shown in the diagram.
- Connect wire BK2 to terminal 18 and BK3 to terminal 19. Do not reverse them.
- Wire the blower to the adaptor as shown in the diagram.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.