Viessmann Boiler: Clock the natural gas meter to verify input
Clock the natural gas meter to verify input on a Viessmann boiler: Time the meter to check the boiler gas input. Only use this method at low altitude. Get the heating value from the gas supplier before timing.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Common causes of clock the natural gas meter to verify input
- Gas input too high or too low
How to fix clock the natural gas meter to verify input: step by step
- Turn off all other gas appliances served by the meter.
- Time how many seconds the boiler takes to use 10 ft³ of gas.
- Multiply 3600 by 10, then divide by the seconds measured.
- Multiply that result by the gas heating value in Btu per ft³ (or use the nominal 1000 Btu/ft³ if the supplier value is not available).
- Compare the result to the boiler input rating.
- A boiler underfired by up to 5% is acceptable. Do not overfire the boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.