Viessmann Boiler: Clearances to combustibles and service access
Clearances to combustibles and service access on a Viessmann boiler: Values read from the clearance tables. The printed table layout is jumbled in the text, so confirm each figure against the page before use.
Applies to: VR1 22 to 33, 91 to 140
How to fix clearances to combustibles and service access: step by step
- Standard installation: keep the rear 6 in (150 mm) and flue 9 in (230 mm) from combustibles. Sides are 0 in.
- Floor combustibles: confirm the rear, side, flue and top values on the printed table.
- Alcove installation: allow 24 in (610 mm) for burner service.
- Keep the minimum service access shown in the recommended clearances for service diagram for cleaning and service.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.